power to current calculator
Convert electrical power (W) to current (A) for DC, single-phase AC, and three-phase AC. Enter power, voltage, and power factor to get accurate RMS or DC current.

three-phase current calculator
Divide voltage by power and add in the power factor; multiply voltage by 1.732 to calculate line currents in three times a three-phase circuit.
Formula & Table Summary:
DC: I = P / V
1-phase AC: I = P / (V · PF)
3-phase AC: I = P / (√3 · V_LL · PF)
Inputs: P (W), V (V), PF (0–1). Output: I (A).
apparent current calculator
Enter Power (W), Voltage (V), and Power Factor (PF) to calculate current (A) with DC, single-phase ac or three-phase ac using the correct formula.Use this calculator to use in speedily circuit sizing checks, selecting breakers, energy audits, and determining that conductors or protective devices are not overloaded. Note:in apparent power (VA) or with line-to-neutral voltage on three-phase systems multiply voltage input by powers of two; reduce formula to the order of theSIGMAS.
watts to amps calculator
| Type | P (W) | V (V) | PF | I (A) |
|---|---|---|---|---|
| DC | 1200 | 48 | 1.00 | 25.0000 |
| 1-phase | 2300 | 230 | 0.80 | 12.5000 |
| 1-phase | 5000 | 120 | 0.95 | 43.8596 |
| 3-phase | 10000 | 415 | 0.90 | 15.4578 |
| 3-phase | 50000 | 11000 | 0.85 | 3.0874 |
Frequently Asked Questions - power to current calculator:
How do I calculate current from power for DC?
Use I = P / V (amps = watts ÷ volts).
What formula for single-phase AC with power factor?
I = P / (V · PF), where PF is 0–1 (use 1 for purely resistive loads).
What about three-phase systems?
Use I = P / (√3 · V_LL · PF) where V_LL is line-to-line voltage and PF is power factor.
If I only know VA (apparent power), what do I use?
For single-phase: I = S / V. For three-phase: I = S / (√3 · V_LL).
Can current exceed power divided by phase voltage?
If PF < 1, current will be higher than P/V because real power is reduced by PF; use PF in the denominator.
What power factor should I assume if unknown?
If unknown and load is likely resistive, assume PF ≈1. For motors or inductive loads, assume PF 0.8–0.9 unless measured.
Does this include starting/inrush currents?
No. These formulas give steady-state RMS current from steady real power. Motor starting and inrush require separate transient calculations.
How to size a breaker from calculated current?
Choose next standard breaker rating above the continuous load plus apply code derating (e.g., 125% for continuous loads per many electrical codes). Verify with local rules.
Are harmonic currents included?
No. Harmonics (from non-linear loads) increase RMS current; use measurements or harmonic analysis for accurate sizing.
What voltage should I use for 3-phase Y (wye) systems?
Use line-to-line voltage (V_LL) with the √3 formula for line current. If you must use V_LN, convert or use phase formulas accordingly.
Related Posts

current imbalance calculator
Calculate percentage current imbalance in three-phase systems using % I imb= {(Imax - Iavg) / Iavg} * 100

instantaneous current calculator
Calculate instantaneous current in AC or DC circuits using voltage, resistance, and time-dependent waveforms with accuracy.

Watts to Amps Calculator
Quickly convert watts to amps using this free online calculator. Works for DC, single-phase, and three-phase AC systems. Instant, accurate electrical conversions.

Watts to btu per hours calculator
Convert watts (W) to BTU per hour (BTU/h) easily. 1 W = 3.412141633 BTU/h. Perfect for HVAC, heating, and cooling capacity conversions.

dbm to rms voltage calculator
Convert dBm power levels to RMS voltage easily using impedance and power formulas. Ideal for RF engineers and audio signal analysis.

No-load voltage calculator
Calculate the no-load (open circuit) voltage of generators, transformers, or other sources using EMF equations, winding data, and test parameters.